SPring-8, the large synchrotron radiation facility

Skip to content
» JAPANESE
Personal tools
 

Outline of Experimental Drainage Treatment Facility

(1) Treatment of experimental drainage

  1. Treatment capacity   250 m3/day
  2. Treatment process
    raw water control → coagulation - precipitation with agent addition → filtration through sand / activated carbon → chelation treatment for mercury and heavy metal removal
    Discharged into sewerage after confirmation that analyzed values are under Effluent Standards.
    *Effluent Standards : standards are specified by Harima-Kogen Wide-Area Union (based on Water Pollution Control Law.)


(2) Automatic analyzer equipment of water quality

  1. Raw water autoanalyzer
    To protect the facility, autoanalyzers are installed to detect the raw water that doesn't fit acceptance criteria.
    Analyzer
    Fluoride ion, Total-chromium, Total-cyanogen, Mercury, Oils, Phenol, Manganese
  2. Treated water autoanalyzer
    Twelve analyzers are currently in operation.
    Analyzer
    Cadmium, Cyanogen, Hexavalent chromium, Arsenic, Lead, Fluoride ion, Total-chromium, Total-cyanogen, Mercury, Oils, Phenol, Manganese
Last modified 2011-09-01 14:14